Fiber and cabling
Fiber types: OS2, OM3, OM4 and the rest
OS2 is single-mode fiber (9 µm core) for links from a few metres to tens of kilometres; OM3 and OM4 are laser-optimised 50 µm multimode fibers for short, high-speed links inside buildings and data centres. OM4 has a higher modal bandwidth than OM3, so the same transceiver reaches further: 150 m instead of 100 m at 40GBASE-SR4.
- Classes are defined in ISO/IEC 11801 and TIA-568.3-D. OM1 is 62.5/125 µm, OM2 to OM5 are 50/125 µm, OS1a and OS2 are 9/125 µm single-mode.
- Effective modal bandwidth at 850 nm: OM3 2000 MHz·km, OM4 4700 MHz·km. OM5 adds a specified bandwidth up to 953 nm for short-wavelength multiplexing (SWDM).
- Maximum cabled attenuation in ISO/IEC 11801: multimode 3.5 dB/km at 850 nm and 1.5 dB/km at 1300 nm; OS2 0.4 dB/km at 1310 and 1550 nm.
- Jacket colours under TIA-598-C: OM1 and OM2 orange, OM3 aqua, OM4 aqua (violet is common in Europe), OM5 lime green, single-mode yellow. Tactical and outdoor cables are usually black or olive whatever the fiber inside.
- Single-mode transceivers cost more, but the fiber itself is cheaper and future-proof. For anything over about 400 m, or any link that may later carry higher speeds, OS2 is the safe choice.
- Bend-insensitive single-mode (ITU-T G.657.A1 or A2) tolerates tighter routing than standard G.652.D and stays compatible with it.
| Application | OM3 | OM4 | OS2 |
|---|---|---|---|
| 1000BASE-SX / LX (1G) | 550 m | 550 m | 5 km (LX) |
| 10GBASE-SR / LR (10G) | 300 m | 400 m | 10 km (LR) |
| 25GBASE-SR (25G) | 70 m | 100 m | 10 km (LR) |
| 40GBASE-SR4 / LR4 (40G) | 100 m | 150 m | 10 km (LR4) |
| 100GBASE-SR4 / LR4 (100G) | 70 m | 100 m | 10 km (LR4) |
Multimode figures are for 850 nm parallel or serial optics; single-mode figures for 1310 nm LR optics (ER optics reach 40 km). Extended-reach multimode transceivers exist, but these are the standard values to design against.
On your RFQ: Fiber class (OS2, OM3, OM4), fiber count, and the transceiver or interface you plan to run.
Connectors
IEC 61754 connector families: LC, SC, ST, FC, MPO, SMA
IEC 61754 is the international series that fixes the mating dimensions of fiber optic connector families, so an LC from one maker mates with an LC from another. Each family has its own part: for example IEC 61754-20 for LC, 61754-4 for SC and 61754-7 for MPO.
- LC (61754-20) uses a 1.25 mm ferrule and a push-pull latch. It is the default for duplex links in racks and transceivers because it is half the size of SC.
- SC (61754-4) uses a 2.5 mm ferrule and a push-pull square body. Common in telecom, FTTH and older equipment.
- ST, formally BFOC/2.5 (61754-2), uses a bayonet coupling on a 2.5 mm ferrule. Still widespread in industrial, campus and broadcast installations.
- FC (61754-13) has a threaded coupling nut on a 2.5 mm ferrule. It resists vibration and is common on test equipment and in some telecom and sensing systems.
- MPO (61754-7) holds 8, 12, 16 or 24 fibers in one rectangular ferrule, with guide pins on the male side. MTP is a brand of MPO-compatible connector. Polarity follows TIA-568 methods A, B or C.
- F-SMA (61754-22), usually called SMA 905, has a threaded nut and no physical contact between fibers. It is the usual choice for laser delivery, spectroscopy, sensing and PCF links.
- The connector body colour usually tells you the polish: blue for single-mode UPC, green for single-mode APC, beige or aqua for multimode.
| Family | IEC 61754 part | Ferrule | Coupling | Typical use |
|---|---|---|---|---|
| LC | -20 | 1.25 mm | Push-pull latch | Transceivers, racks, dense patching |
| SC | -4 | 2.5 mm | Push-pull | Telecom, FTTH, older equipment |
| ST (BFOC/2.5) | -2 | 2.5 mm | Bayonet | Industrial, campus, broadcast |
| FC | -13 | 2.5 mm | Threaded | Test gear, vibration, sensing |
| MPO / MTP | -7 | MT, 8 to 24 fibers | Push-pull | Data centre trunks, 40G and 100G |
| SMA 905 (F-SMA) | -22 | 3.175 mm, no contact | Threaded | Laser, sensing, PCF links |
On your RFQ: Connector family at each end, polish (UPC or APC), and for MPO the fiber count, gender and polarity method.
Connectors
End-face polish: PC, UPC and APC
The polish on a ferrule end-face controls how much light reflects back down the fiber. UPC (ultra physical contact) gives a return loss of about 50 dB or better; APC (angled physical contact, 8 degrees) gives about 60 dB or better and is used where reflections matter, such as RF over fiber, FTTH video and some sensing systems.
- UPC and APC connectors must never be mated with each other: the angled face leaves an air gap and can damage both ends.
- TIA-568.3-D allows up to 0.75 dB per mated connector pair in a link budget. A well-made single-mode UPC pair usually measures 0.3 dB or less.
- End-face geometry (radius of curvature, apex offset, fiber height) is specified in IEC 61755-3 and checked with an interferometer.
- Cleanliness matters more than polish once a cable is in service. IEC 61300-3-35 sets pass and fail criteria for scratches and contamination by zone.
On your RFQ: UPC or APC, and the maximum insertion loss and minimum return loss you need per connector.
Fiber and cabling
TIA-568: structured cabling for fiber and copper
TIA-568 is the North American standard set for structured cabling in commercial buildings: TIA-568.2-D covers balanced twisted-pair copper (Category 6, 6A) and TIA-568.3-D covers optical fiber components and link budgets. ISO/IEC 11801 is the international counterpart.
- A twisted-pair channel is limited to 100 m: a 90 m permanent link plus up to 10 m of patch cords in total.
- Category 6 is specified to 250 MHz and supports 10GBASE-T only over shorter runs (about 37 to 55 m depending on alien crosstalk). Category 6A is specified to 500 MHz and supports 10GBASE-T to the full 100 m.
- T568A and T568B are the two RJ45 pin assignments. Either works if both ends match; mixing them makes a crossover cable.
- Fiber link loss budgets in TIA-568.3-D allow 0.75 dB per mated connector pair, 0.3 dB per splice, plus the fiber attenuation per kilometre.
- MPO polarity methods A, B and C in TIA-568.3-D define how fiber positions flip from one end of a trunk to the other so that transmit meets receive.
- LSZH (low smoke zero halogen) jackets are often required in data centres, ships, tunnels and public buildings; IEC 60332 covers flame propagation and IEC 61034 smoke density.
| Category | Bandwidth | 10GBASE-T reach | Typical use |
|---|---|---|---|
| Cat 5e | 100 MHz | Not supported | 1G desk links |
| Cat 6 | 250 MHz | About 37 to 55 m | 1G links, short 10G, stage snakes |
| Cat 6A | 500 MHz | 100 m | 10G, Wi-Fi access points, PoE |
On your RFQ: Category, shielding (UTP, F/UTP or S/FTP), jacket (PVC or LSZH), length and boot style.
Military
MIL-DTL-38999: circular connectors
MIL-DTL-38999 is the US military specification for high-density, environment-resistant circular connectors, used across aircraft, vehicles, ships and ground systems. Its fiber optic versions carry MIL-PRF-29504 termini in place of electrical contacts, often mixed with copper contacts in the same shell.
- There are four series. Series III, with a triple-start threaded coupling nut, is the most widely used. Series I and II are bayonet-coupled; Series IV uses a breech-lock coupling.
- Shell sizes run from 9 to 25. Insert arrangements fix how many contacts or termini fit and in what positions.
- Fiber termini are usually size 16, so a size 25 Series III shell can carry dozens of fibers.
- The shell's temperature rating depends on class and plating. In a finished fiber assembly the cable jacket, epoxy and boot usually set the real limit, so ask for the rating of the complete assembly, not just the connector.
- Plating choices include olive drab cadmium, black zinc-nickel and nickel; zinc-nickel is the usual cadmium-free option.
- Many commercial connectors are "38999-style" or "38999-intermateable" without being qualified parts. If a programme needs qualified parts, say so on the RFQ.
On your RFQ: Series, shell size, insert arrangement, plug or receptacle, plating, and whether QPL-listed parts are mandatory.
Military
MIL-PRF-29504: fiber optic termini
MIL-PRF-29504 specifies the fiber optic termini, the pin and socket contacts that hold each fiber inside a multi-way military connector such as MIL-DTL-38999. Slash sheets /4 (pin) and /5 (socket) are the common size 16 termini.
- Each terminus is a precision ceramic ferrule in a metal body. Fibers are epoxied and polished in the terminus before it is inserted into the connector insert.
- The socket side carries an alignment sleeve; the pin side is spring-loaded so the end-faces butt together under controlled force.
- Because the fibers touch, termini must be inspected and cleaned like any physical-contact connector. Removable inserts or alignment sleeves make cleaning possible in the field.
- Loss per mated pair depends on fiber type and the connector maker's datasheet. Ask for measured values per channel on the test report.
On your RFQ: Terminus type, fiber type and core size, and the maximum insertion loss per channel.
Military
MIL-DTL-83526: hermaphroditic tactical connectors
MIL-DTL-83526 covers hermaphroditic, low-force, environment-resistant fiber optic connectors for tactical field cables, the family that includes TFOCA-II style 2 and 4 channel connectors. Because every connector is identical, any cable end mates with any other, so reels can be daisy-chained in the field without adaptors.
- Each connector has both pin and socket positions, so the same part sits at both ends of every cable.
- They are physical-contact connectors: low loss when clean, but they need dust caps fitted and cleaning before every mate.
- Common builds are 2 or 4 channel multimode or single-mode, on armoured or polyurethane tactical cable wound onto reels.
- Typical uses are field command posts, deployable radar and communications shelters, and outside broadcast, where crews join and split cables under time pressure.
- The cable itself is often specified to MIL-PRF-85045, the US military general specification for fiber optic cables, which covers constructions such as tight-buffered tactical cable.
On your RFQ: Channel count, fiber type, cable length per reel, and whether you need receptacles for shelters or panels.
Connectors
Expanded beam vs physical contact
A physical-contact connector butts two polished fiber ends together; an expanded-beam connector uses lenses to widen the light to a beam many times the core diameter and refocus it on the other side, with an air gap between the halves. Expanded beam costs a little more loss but tolerates dust, mud and water and can be cleaned with a wipe.
- A speck of dust on a 9 µm single-mode core can block most of the light. On an expanded beam of around a millimetre, the same speck blocks only a small fraction.
- Typical insertion loss: physical-contact pairs about 0.2 to 0.5 dB; expanded-beam pairs about 0.5 to 1.5 dB depending on fiber type and lens design.
- Expanded-beam lenses do not touch, so mating cycles run into the thousands with little wear.
- MIL-PRF-64266 is the US military specification for expanded-beam circular connectors. Many commercial expanded-beam connectors exist outside it.
- Physical contact remains the right choice for clean, fixed, low-loss links: racks, buildings, sealed enclosures.
| Physical contact | Expanded beam | |
|---|---|---|
| How light crosses | Polished fiber ends touch | Lenses, air gap between halves |
| Typical loss per mated pair | About 0.2 to 0.5 dB | About 0.5 to 1.5 dB |
| Dirt tolerance | Low: one particle can fail a link | High: wipe and mate |
| Field cleaning | Tools and inspection scope | Lint-free wipe, water rinse |
| Mating cycles | Hundreds to low thousands | Thousands |
| Best for | Clean, fixed installations | Field, mud, sand, salt spray |
On your RFQ: How often the connector will be mated, where (indoor, field, offshore), and the total loss budget for the link.
Broadcast
SMPTE 304M and 311M: hybrid camera cable
SMPTE 311M defines the hybrid fiber and copper cable used between broadcast cameras and their camera control units, and SMPTE 304M defines the matching connector. The cable carries two single-mode fibers for signals and copper conductors for power and control in one jacket.
- The cable has two single-mode fibers, two heavier conductors for camera power and two lighter conductors for low-voltage control, inside an overall jacket with strength members.
- The 304M connector is the hybrid plug and receptacle widely made in the LEMO 3K.93C format and compatible equivalents. Japanese systems often use the ARIB standard instead; the two do not intermate.
- The fiber could run for kilometres. In practice the length is limited by voltage drop on the power conductors, so each camera and CCU maker publishes a maximum length.
- The fiber contacts are physical-contact and sit at the face of the connector, so caps must stay on and both halves must be cleaned before every connection.
- Tactical versions add a tougher polyurethane jacket for outside broadcast cable runs and drums.
On your RFQ: Length, connector format (304M or ARIB), jacket type, and whether you need a drum, panel receptacles or extension adaptors.
Broadcast
SDI: SMPTE 259M to ST 2082 (12G)
SDI (serial digital interface) is the uncompressed video interface used in broadcast, carried on 75 ohm coax with BNC connectors or on fiber. The grade sets the data rate: HD-SDI is 1.485 Gb/s (SMPTE 292), 3G-SDI is 2.97 Gb/s (SMPTE 424M), 6G-SDI is about 6 Gb/s (ST 2081) and 12G-SDI is about 12 Gb/s (ST 2082).
- Higher data rates lose more signal per metre of coax, so 12G-SDI reaches far less distance than HD-SDI on the same cable.
- Coax reach depends on the cable and on the equaliser in the receiving equipment. Treat the figures below as typical for a good RG6-class 75 ohm cable and check the cable maker's tables.
- For longer runs, SDI goes onto fiber: SMPTE 297 defines the optical interface, and single-mode fiber carries 12G-SDI for kilometres.
- Use true 75 ohm BNC connectors rated for the data rate. A 50 ohm BNC or a poor crimp causes reflections that close the eye at 12G.
| Grade | Standard | Data rate | Typical formats | Typical coax reach |
|---|---|---|---|---|
| SD-SDI | SMPTE 259M | 270 Mb/s | 576i, 480i | About 300 m |
| HD-SDI | SMPTE 292 | 1.485 Gb/s | 720p, 1080i | About 100 to 140 m |
| 3G-SDI | SMPTE 424M | 2.97 Gb/s | 1080p50/60 | About 70 to 100 m |
| 6G-SDI | SMPTE ST 2081 | 5.94 Gb/s | 2160p30 | About 50 to 80 m |
| 12G-SDI | SMPTE ST 2082 | 11.88 Gb/s | 2160p50/60 | About 30 to 70 m |
Typical values for RG6-class 75 ohm cable. Thinner cables (RG59, mini coax) reach much less.
On your RFQ: SDI grade, length, cable size, connector (BNC or HD-BNC), and whether a fiber conversion is acceptable for long runs.
Environment
IP67 and IP68: ingress protection
IP ratings under IEC 60529 state how well an enclosure or connector keeps out solids and water. IP67 means dust-tight and protected against temporary immersion to 1 m for 30 minutes; IP68 means dust-tight and protected against continuous immersion under conditions the manufacturer states, which must be harsher than IP67.
- The first digit is solids (6 is dust-tight), the second is water (7 is temporary immersion, 8 is continuous immersion).
- IP68 has no fixed depth or time in the standard. Always ask for the stated depth and duration, for example 10 m for 24 hours.
- A connector's IP rating normally applies when mated, or unmated with its dust cap fitted. An open receptacle has no rating.
- IP69K, from ISO 20653, covers high-pressure, high-temperature washdown. It is a different test, not a higher grade of IP68.
- Salt spray and UV are separate concerns. For offshore and marine use, specify jacket material and plating as well as the IP rating.
| Code | Solids | Water |
|---|---|---|
| IP65 | Dust-tight | Water jets from any direction |
| IP66 | Dust-tight | Powerful water jets |
| IP67 | Dust-tight | Temporary immersion, 1 m for 30 minutes |
| IP68 | Dust-tight | Continuous immersion, depth and time stated by maker |
On your RFQ: The IP rating mated and unmated, and for IP68 the depth and duration you need.
Environment
RoHS and REACH: restricted substances
RoHS (EU Directive 2011/65/EU and its amendments) restricts ten substances in electrical and electronic equipment, including lead, mercury, cadmium and hexavalent chromium, to 0.1 percent by weight of each homogeneous material (0.01 percent for cadmium). REACH (EC 1907/2006) requires suppliers to declare substances of very high concern above 0.1 percent by weight in an article.
- The ten RoHS substances are lead, mercury, cadmium, hexavalent chromium, PBB, PBDE and four phthalates (DEHP, BBP, DBP, DIBP).
- Olive drab cadmium plating, common on military circular connectors, is not RoHS compliant. Defence equipment is often outside RoHS scope, but if your product needs compliance, choose a cadmium-free finish such as zinc-nickel.
- Compliance is shown by a supplier declaration backed by material data for each component: connectors, cable jacket, boots, epoxy and labels.
- The UK has equivalent RoHS and REACH regimes after Brexit; many other markets have similar rules.
On your RFQ: Whether RoHS or REACH declarations are required for the assembly, and for which market.
Industrial links
POF and PCF: plastic and plastic-clad fiber
POF (plastic optical fiber, typically 980/1000 µm PMMA) and PCF (plastic-clad silica, typically 200/230 µm) are large-core fibers for short industrial links. They carry control signals through high electrical noise with full galvanic isolation, and they are easy to terminate in the field.
- POF works at visible red (650 nm) with an attenuation of roughly 0.15 to 0.2 dB per metre, so links are usually tens of metres.
- PCF has a silica core and polymer cladding. Its attenuation is a few dB per kilometre at 650 to 850 nm, so it reaches hundreds of metres in the same kind of system.
- Typical uses are gate drive and feedback in power electronics, variable-speed drives, inverters, wind turbine converters, HVDC valves and PLC networks.
- Common connectors are HFBR-style (Versatile Link) and TOCP-style for POF, and SMA 905, ST and V-pin for PCF. The connector must match the transmitter and receiver on the equipment.
- Neither type is a substitute for glass fiber over long distances or at high data rates. They are chosen for noise immunity, isolation and easy handling.
| POF | PCF (HCS) | Glass multimode | |
|---|---|---|---|
| Core / cladding | 980/1000 µm | 200/230 µm | 50/125 µm |
| Working wavelength | 650 nm | 650 to 850 nm | 850 and 1300 nm |
| Typical attenuation | 150 to 200 dB/km | About 6 to 10 dB/km | 3.5 dB/km at 850 nm |
| Typical link length | Up to about 50 m | Up to a few hundred metres | Hundreds of metres to km |
| Typical connectors | HFBR-style, TOCP-style | SMA 905, ST, V-pin, HFBR-style | LC, SC, ST, MPO |
On your RFQ: Fiber type, connector at each end (match the equipment port), length, simplex or duplex, and jacket.