Telespace Networks

Standards reference

Fiber optic and cabling standards, explained.

A plain-language reference to the standards that decide how fiber and copper links are specified: fiber types and their reach, connector families, structured cabling, military connectors, broadcast interfaces, ingress protection and industrial plastic fiber. Written for engineers and buyers who need the right number quickly.

Updated 27 November 2026. General reference, not a substitute for the published standard.

Fiber and cabling

Fiber types: OS2, OM3, OM4 and the rest

OS2 is single-mode fiber (9 µm core) for links from a few metres to tens of kilometres; OM3 and OM4 are laser-optimised 50 µm multimode fibers for short, high-speed links inside buildings and data centres. OM4 has a higher modal bandwidth than OM3, so the same transceiver reaches further: 150 m instead of 100 m at 40GBASE-SR4.

  • Classes are defined in ISO/IEC 11801 and TIA-568.3-D. OM1 is 62.5/125 µm, OM2 to OM5 are 50/125 µm, OS1a and OS2 are 9/125 µm single-mode.
  • Effective modal bandwidth at 850 nm: OM3 2000 MHz·km, OM4 4700 MHz·km. OM5 adds a specified bandwidth up to 953 nm for short-wavelength multiplexing (SWDM).
  • Maximum cabled attenuation in ISO/IEC 11801: multimode 3.5 dB/km at 850 nm and 1.5 dB/km at 1300 nm; OS2 0.4 dB/km at 1310 and 1550 nm.
  • Jacket colours under TIA-598-C: OM1 and OM2 orange, OM3 aqua, OM4 aqua (violet is common in Europe), OM5 lime green, single-mode yellow. Tactical and outdoor cables are usually black or olive whatever the fiber inside.
  • Single-mode transceivers cost more, but the fiber itself is cheaper and future-proof. For anything over about 400 m, or any link that may later carry higher speeds, OS2 is the safe choice.
  • Bend-insensitive single-mode (ITU-T G.657.A1 or A2) tolerates tighter routing than standard G.652.D and stays compatible with it.
Maximum reach by fiber type (IEEE 802.3 Ethernet)
ApplicationOM3OM4OS2
1000BASE-SX / LX (1G)550 m550 m5 km (LX)
10GBASE-SR / LR (10G)300 m400 m10 km (LR)
25GBASE-SR (25G)70 m100 m10 km (LR)
40GBASE-SR4 / LR4 (40G)100 m150 m10 km (LR4)
100GBASE-SR4 / LR4 (100G)70 m100 m10 km (LR4)

Multimode figures are for 850 nm parallel or serial optics; single-mode figures for 1310 nm LR optics (ER optics reach 40 km). Extended-reach multimode transceivers exist, but these are the standard values to design against.

On your RFQ: Fiber class (OS2, OM3, OM4), fiber count, and the transceiver or interface you plan to run.

Connectors

IEC 61754 connector families: LC, SC, ST, FC, MPO, SMA

IEC 61754 is the international series that fixes the mating dimensions of fiber optic connector families, so an LC from one maker mates with an LC from another. Each family has its own part: for example IEC 61754-20 for LC, 61754-4 for SC and 61754-7 for MPO.

  • LC (61754-20) uses a 1.25 mm ferrule and a push-pull latch. It is the default for duplex links in racks and transceivers because it is half the size of SC.
  • SC (61754-4) uses a 2.5 mm ferrule and a push-pull square body. Common in telecom, FTTH and older equipment.
  • ST, formally BFOC/2.5 (61754-2), uses a bayonet coupling on a 2.5 mm ferrule. Still widespread in industrial, campus and broadcast installations.
  • FC (61754-13) has a threaded coupling nut on a 2.5 mm ferrule. It resists vibration and is common on test equipment and in some telecom and sensing systems.
  • MPO (61754-7) holds 8, 12, 16 or 24 fibers in one rectangular ferrule, with guide pins on the male side. MTP is a brand of MPO-compatible connector. Polarity follows TIA-568 methods A, B or C.
  • F-SMA (61754-22), usually called SMA 905, has a threaded nut and no physical contact between fibers. It is the usual choice for laser delivery, spectroscopy, sensing and PCF links.
  • The connector body colour usually tells you the polish: blue for single-mode UPC, green for single-mode APC, beige or aqua for multimode.
Common connector families at a glance
FamilyIEC 61754 partFerruleCouplingTypical use
LC-201.25 mmPush-pull latchTransceivers, racks, dense patching
SC-42.5 mmPush-pullTelecom, FTTH, older equipment
ST (BFOC/2.5)-22.5 mmBayonetIndustrial, campus, broadcast
FC-132.5 mmThreadedTest gear, vibration, sensing
MPO / MTP-7MT, 8 to 24 fibersPush-pullData centre trunks, 40G and 100G
SMA 905 (F-SMA)-223.175 mm, no contactThreadedLaser, sensing, PCF links

On your RFQ: Connector family at each end, polish (UPC or APC), and for MPO the fiber count, gender and polarity method.

Connectors

End-face polish: PC, UPC and APC

The polish on a ferrule end-face controls how much light reflects back down the fiber. UPC (ultra physical contact) gives a return loss of about 50 dB or better; APC (angled physical contact, 8 degrees) gives about 60 dB or better and is used where reflections matter, such as RF over fiber, FTTH video and some sensing systems.

  • UPC and APC connectors must never be mated with each other: the angled face leaves an air gap and can damage both ends.
  • TIA-568.3-D allows up to 0.75 dB per mated connector pair in a link budget. A well-made single-mode UPC pair usually measures 0.3 dB or less.
  • End-face geometry (radius of curvature, apex offset, fiber height) is specified in IEC 61755-3 and checked with an interferometer.
  • Cleanliness matters more than polish once a cable is in service. IEC 61300-3-35 sets pass and fail criteria for scratches and contamination by zone.

On your RFQ: UPC or APC, and the maximum insertion loss and minimum return loss you need per connector.

Fiber and cabling

TIA-568: structured cabling for fiber and copper

TIA-568 is the North American standard set for structured cabling in commercial buildings: TIA-568.2-D covers balanced twisted-pair copper (Category 6, 6A) and TIA-568.3-D covers optical fiber components and link budgets. ISO/IEC 11801 is the international counterpart.

  • A twisted-pair channel is limited to 100 m: a 90 m permanent link plus up to 10 m of patch cords in total.
  • Category 6 is specified to 250 MHz and supports 10GBASE-T only over shorter runs (about 37 to 55 m depending on alien crosstalk). Category 6A is specified to 500 MHz and supports 10GBASE-T to the full 100 m.
  • T568A and T568B are the two RJ45 pin assignments. Either works if both ends match; mixing them makes a crossover cable.
  • Fiber link loss budgets in TIA-568.3-D allow 0.75 dB per mated connector pair, 0.3 dB per splice, plus the fiber attenuation per kilometre.
  • MPO polarity methods A, B and C in TIA-568.3-D define how fiber positions flip from one end of a trunk to the other so that transmit meets receive.
  • LSZH (low smoke zero halogen) jackets are often required in data centres, ships, tunnels and public buildings; IEC 60332 covers flame propagation and IEC 61034 smoke density.
Copper categories for Ethernet
CategoryBandwidth10GBASE-T reachTypical use
Cat 5e100 MHzNot supported1G desk links
Cat 6250 MHzAbout 37 to 55 m1G links, short 10G, stage snakes
Cat 6A500 MHz100 m10G, Wi-Fi access points, PoE

On your RFQ: Category, shielding (UTP, F/UTP or S/FTP), jacket (PVC or LSZH), length and boot style.

Military

MIL-DTL-38999: circular connectors

MIL-DTL-38999 is the US military specification for high-density, environment-resistant circular connectors, used across aircraft, vehicles, ships and ground systems. Its fiber optic versions carry MIL-PRF-29504 termini in place of electrical contacts, often mixed with copper contacts in the same shell.

  • There are four series. Series III, with a triple-start threaded coupling nut, is the most widely used. Series I and II are bayonet-coupled; Series IV uses a breech-lock coupling.
  • Shell sizes run from 9 to 25. Insert arrangements fix how many contacts or termini fit and in what positions.
  • Fiber termini are usually size 16, so a size 25 Series III shell can carry dozens of fibers.
  • The shell's temperature rating depends on class and plating. In a finished fiber assembly the cable jacket, epoxy and boot usually set the real limit, so ask for the rating of the complete assembly, not just the connector.
  • Plating choices include olive drab cadmium, black zinc-nickel and nickel; zinc-nickel is the usual cadmium-free option.
  • Many commercial connectors are "38999-style" or "38999-intermateable" without being qualified parts. If a programme needs qualified parts, say so on the RFQ.

On your RFQ: Series, shell size, insert arrangement, plug or receptacle, plating, and whether QPL-listed parts are mandatory.

Military

MIL-PRF-29504: fiber optic termini

MIL-PRF-29504 specifies the fiber optic termini, the pin and socket contacts that hold each fiber inside a multi-way military connector such as MIL-DTL-38999. Slash sheets /4 (pin) and /5 (socket) are the common size 16 termini.

  • Each terminus is a precision ceramic ferrule in a metal body. Fibers are epoxied and polished in the terminus before it is inserted into the connector insert.
  • The socket side carries an alignment sleeve; the pin side is spring-loaded so the end-faces butt together under controlled force.
  • Because the fibers touch, termini must be inspected and cleaned like any physical-contact connector. Removable inserts or alignment sleeves make cleaning possible in the field.
  • Loss per mated pair depends on fiber type and the connector maker's datasheet. Ask for measured values per channel on the test report.

On your RFQ: Terminus type, fiber type and core size, and the maximum insertion loss per channel.

Military

MIL-DTL-83526: hermaphroditic tactical connectors

MIL-DTL-83526 covers hermaphroditic, low-force, environment-resistant fiber optic connectors for tactical field cables, the family that includes TFOCA-II style 2 and 4 channel connectors. Because every connector is identical, any cable end mates with any other, so reels can be daisy-chained in the field without adaptors.

  • Each connector has both pin and socket positions, so the same part sits at both ends of every cable.
  • They are physical-contact connectors: low loss when clean, but they need dust caps fitted and cleaning before every mate.
  • Common builds are 2 or 4 channel multimode or single-mode, on armoured or polyurethane tactical cable wound onto reels.
  • Typical uses are field command posts, deployable radar and communications shelters, and outside broadcast, where crews join and split cables under time pressure.
  • The cable itself is often specified to MIL-PRF-85045, the US military general specification for fiber optic cables, which covers constructions such as tight-buffered tactical cable.

On your RFQ: Channel count, fiber type, cable length per reel, and whether you need receptacles for shelters or panels.

Connectors

Expanded beam vs physical contact

A physical-contact connector butts two polished fiber ends together; an expanded-beam connector uses lenses to widen the light to a beam many times the core diameter and refocus it on the other side, with an air gap between the halves. Expanded beam costs a little more loss but tolerates dust, mud and water and can be cleaned with a wipe.

  • A speck of dust on a 9 µm single-mode core can block most of the light. On an expanded beam of around a millimetre, the same speck blocks only a small fraction.
  • Typical insertion loss: physical-contact pairs about 0.2 to 0.5 dB; expanded-beam pairs about 0.5 to 1.5 dB depending on fiber type and lens design.
  • Expanded-beam lenses do not touch, so mating cycles run into the thousands with little wear.
  • MIL-PRF-64266 is the US military specification for expanded-beam circular connectors. Many commercial expanded-beam connectors exist outside it.
  • Physical contact remains the right choice for clean, fixed, low-loss links: racks, buildings, sealed enclosures.
Expanded beam vs physical contact
Physical contactExpanded beam
How light crossesPolished fiber ends touchLenses, air gap between halves
Typical loss per mated pairAbout 0.2 to 0.5 dBAbout 0.5 to 1.5 dB
Dirt toleranceLow: one particle can fail a linkHigh: wipe and mate
Field cleaningTools and inspection scopeLint-free wipe, water rinse
Mating cyclesHundreds to low thousandsThousands
Best forClean, fixed installationsField, mud, sand, salt spray

On your RFQ: How often the connector will be mated, where (indoor, field, offshore), and the total loss budget for the link.

Broadcast

SMPTE 304M and 311M: hybrid camera cable

SMPTE 311M defines the hybrid fiber and copper cable used between broadcast cameras and their camera control units, and SMPTE 304M defines the matching connector. The cable carries two single-mode fibers for signals and copper conductors for power and control in one jacket.

  • The cable has two single-mode fibers, two heavier conductors for camera power and two lighter conductors for low-voltage control, inside an overall jacket with strength members.
  • The 304M connector is the hybrid plug and receptacle widely made in the LEMO 3K.93C format and compatible equivalents. Japanese systems often use the ARIB standard instead; the two do not intermate.
  • The fiber could run for kilometres. In practice the length is limited by voltage drop on the power conductors, so each camera and CCU maker publishes a maximum length.
  • The fiber contacts are physical-contact and sit at the face of the connector, so caps must stay on and both halves must be cleaned before every connection.
  • Tactical versions add a tougher polyurethane jacket for outside broadcast cable runs and drums.

On your RFQ: Length, connector format (304M or ARIB), jacket type, and whether you need a drum, panel receptacles or extension adaptors.

Broadcast

SDI: SMPTE 259M to ST 2082 (12G)

SDI (serial digital interface) is the uncompressed video interface used in broadcast, carried on 75 ohm coax with BNC connectors or on fiber. The grade sets the data rate: HD-SDI is 1.485 Gb/s (SMPTE 292), 3G-SDI is 2.97 Gb/s (SMPTE 424M), 6G-SDI is about 6 Gb/s (ST 2081) and 12G-SDI is about 12 Gb/s (ST 2082).

  • Higher data rates lose more signal per metre of coax, so 12G-SDI reaches far less distance than HD-SDI on the same cable.
  • Coax reach depends on the cable and on the equaliser in the receiving equipment. Treat the figures below as typical for a good RG6-class 75 ohm cable and check the cable maker's tables.
  • For longer runs, SDI goes onto fiber: SMPTE 297 defines the optical interface, and single-mode fiber carries 12G-SDI for kilometres.
  • Use true 75 ohm BNC connectors rated for the data rate. A 50 ohm BNC or a poor crimp causes reflections that close the eye at 12G.
SDI grades and typical coax reach
GradeStandardData rateTypical formatsTypical coax reach
SD-SDISMPTE 259M270 Mb/s576i, 480iAbout 300 m
HD-SDISMPTE 2921.485 Gb/s720p, 1080iAbout 100 to 140 m
3G-SDISMPTE 424M2.97 Gb/s1080p50/60About 70 to 100 m
6G-SDISMPTE ST 20815.94 Gb/s2160p30About 50 to 80 m
12G-SDISMPTE ST 208211.88 Gb/s2160p50/60About 30 to 70 m

Typical values for RG6-class 75 ohm cable. Thinner cables (RG59, mini coax) reach much less.

On your RFQ: SDI grade, length, cable size, connector (BNC or HD-BNC), and whether a fiber conversion is acceptable for long runs.

Environment

IP67 and IP68: ingress protection

IP ratings under IEC 60529 state how well an enclosure or connector keeps out solids and water. IP67 means dust-tight and protected against temporary immersion to 1 m for 30 minutes; IP68 means dust-tight and protected against continuous immersion under conditions the manufacturer states, which must be harsher than IP67.

  • The first digit is solids (6 is dust-tight), the second is water (7 is temporary immersion, 8 is continuous immersion).
  • IP68 has no fixed depth or time in the standard. Always ask for the stated depth and duration, for example 10 m for 24 hours.
  • A connector's IP rating normally applies when mated, or unmated with its dust cap fitted. An open receptacle has no rating.
  • IP69K, from ISO 20653, covers high-pressure, high-temperature washdown. It is a different test, not a higher grade of IP68.
  • Salt spray and UV are separate concerns. For offshore and marine use, specify jacket material and plating as well as the IP rating.
Common IP codes for cable assemblies
CodeSolidsWater
IP65Dust-tightWater jets from any direction
IP66Dust-tightPowerful water jets
IP67Dust-tightTemporary immersion, 1 m for 30 minutes
IP68Dust-tightContinuous immersion, depth and time stated by maker

On your RFQ: The IP rating mated and unmated, and for IP68 the depth and duration you need.

Environment

RoHS and REACH: restricted substances

RoHS (EU Directive 2011/65/EU and its amendments) restricts ten substances in electrical and electronic equipment, including lead, mercury, cadmium and hexavalent chromium, to 0.1 percent by weight of each homogeneous material (0.01 percent for cadmium). REACH (EC 1907/2006) requires suppliers to declare substances of very high concern above 0.1 percent by weight in an article.

  • The ten RoHS substances are lead, mercury, cadmium, hexavalent chromium, PBB, PBDE and four phthalates (DEHP, BBP, DBP, DIBP).
  • Olive drab cadmium plating, common on military circular connectors, is not RoHS compliant. Defence equipment is often outside RoHS scope, but if your product needs compliance, choose a cadmium-free finish such as zinc-nickel.
  • Compliance is shown by a supplier declaration backed by material data for each component: connectors, cable jacket, boots, epoxy and labels.
  • The UK has equivalent RoHS and REACH regimes after Brexit; many other markets have similar rules.

On your RFQ: Whether RoHS or REACH declarations are required for the assembly, and for which market.

Industrial links

POF and PCF: plastic and plastic-clad fiber

POF (plastic optical fiber, typically 980/1000 µm PMMA) and PCF (plastic-clad silica, typically 200/230 µm) are large-core fibers for short industrial links. They carry control signals through high electrical noise with full galvanic isolation, and they are easy to terminate in the field.

  • POF works at visible red (650 nm) with an attenuation of roughly 0.15 to 0.2 dB per metre, so links are usually tens of metres.
  • PCF has a silica core and polymer cladding. Its attenuation is a few dB per kilometre at 650 to 850 nm, so it reaches hundreds of metres in the same kind of system.
  • Typical uses are gate drive and feedback in power electronics, variable-speed drives, inverters, wind turbine converters, HVDC valves and PLC networks.
  • Common connectors are HFBR-style (Versatile Link) and TOCP-style for POF, and SMA 905, ST and V-pin for PCF. The connector must match the transmitter and receiver on the equipment.
  • Neither type is a substitute for glass fiber over long distances or at high data rates. They are chosen for noise immunity, isolation and easy handling.
POF vs PCF vs glass multimode
POFPCF (HCS)Glass multimode
Core / cladding980/1000 µm200/230 µm50/125 µm
Working wavelength650 nm650 to 850 nm850 and 1300 nm
Typical attenuation150 to 200 dB/kmAbout 6 to 10 dB/km3.5 dB/km at 850 nm
Typical link lengthUp to about 50 mUp to a few hundred metresHundreds of metres to km
Typical connectorsHFBR-style, TOCP-styleSMA 905, ST, V-pin, HFBR-styleLC, SC, ST, MPO

On your RFQ: Fiber type, connector at each end (match the equipment port), length, simplex or duplex, and jacket.

Questions and answers

Standards questions, answered

What is the difference between OM3 and OM4 fiber?

Both are 50/125 µm laser-optimised multimode fibers with aqua jackets. OM4 has a higher effective modal bandwidth at 850 nm (4700 MHz·km against 2000 MHz·km), so it reaches further at the same speed: 400 m against 300 m at 10G, and 150 m against 100 m at 40GBASE-SR4.

How far can OM3 fiber carry 40G?

100 metres with standard 40GBASE-SR4 optics. Older material that quotes 300 m for OM3 at 40G is wrong; 300 m is the OM3 figure for 10GBASE-SR.

How far can OM4 fiber carry 40G and 100G?

150 metres at 40GBASE-SR4 and 100 metres at 100GBASE-SR4, using standard IEEE 802.3 optics.

When should I choose OS2 single-mode instead of multimode?

Choose OS2 for links longer than a few hundred metres, for any outdoor or campus run, and where the link may later carry higher speeds. OS2 carries 10G and 100G for 10 km with LR optics. Multimode makes sense for short runs inside a room or data centre where cheaper short-reach optics save money.

What colour is single-mode fiber cable?

Under TIA-598-C, single-mode indoor cable is yellow, OM3 and OM4 are aqua (OM4 is often violet in Europe), OM5 is lime green and OM1 and OM2 are orange. Tactical and outdoor cables are usually black or olive, so check the print on the jacket.

What is the difference between UPC and APC connectors?

Both are physical-contact polishes. UPC has a domed flat face and a return loss of about 50 dB or better; APC is polished at 8 degrees and reaches about 60 dB or better. APC connectors are usually green and UPC single-mode connectors blue. Never mate UPC with APC.

How much loss is acceptable per fiber connector?

TIA-568.3-D allows up to 0.75 dB per mated connector pair for link budget purposes. A well-made single-mode LC or SC pair typically measures 0.3 dB or less. Expanded-beam pairs are higher, typically 0.5 to 1.5 dB.

What is the difference between LC and SC connectors?

LC uses a 1.25 mm ferrule and a latch; SC uses a 2.5 mm ferrule and a push-pull square body. Optical performance is similar. LC is half the size, so it is the default for transceivers and dense panels; SC is common in telecom and FTTH.

Is MTP the same as MPO?

MTP is a brand of connector that is compatible with the MPO standard (IEC 61754-7 and TIA-604-5) with tighter mechanical tolerances. MTP and MPO connectors intermate when the gender, fiber count and polarity match.

What are MPO polarity methods A, B and C?

They are the three schemes in TIA-568.3-D for making transmit meet receive across an MPO trunk. Method A uses a straight-through trunk, Method B a flipped trunk with all patch cords the same, and Method C pair-wise flipped fibers. Use one method consistently across a channel.

What is MIL-DTL-38999?

MIL-DTL-38999 is the US military specification for high-density, environment-resistant circular connectors. It has four series; Series III with a threaded coupling is the most common. Fiber versions carry MIL-PRF-29504 termini instead of, or alongside, electrical contacts.

What is the difference between MIL-DTL-38999 and MIL-DTL-83526?

MIL-DTL-38999 connectors are plug and receptacle pairs used on equipment and platforms, with many contacts in one shell. MIL-DTL-83526 connectors are hermaphroditic tactical field connectors, typically 2 or 4 channels, where every end is identical so cables can be joined end to end without adaptors.

What does MIL-PRF-29504 cover?

MIL-PRF-29504 covers fiber optic termini, the pin and socket contacts that hold individual fibers inside multi-way military connectors such as MIL-DTL-38999. Slash sheets /4 and /5 are the common size 16 pin and socket termini.

Is a 38999-style connector the same as a MIL-qualified connector?

No. A 38999-style or intermateable connector follows the same form and mates with qualified parts, but it is not itself listed on the qualified products list. If your programme requires QPL-listed parts, state it on the request for quote.

What is an expanded beam fiber connector?

An expanded beam connector uses lenses to widen the light from the fiber into a beam many times the core size, then refocuses it in the mating half across an air gap. Because the beam is large and the lenses do not touch, it tolerates dirt and water and survives thousands of mating cycles.

Expanded beam or physical contact: which should I choose?

Choose expanded beam for field, offshore, mining and outside broadcast use, where connectors are mated often in dirty conditions. Choose physical contact for clean, fixed installations where the lowest loss matters, such as racks, buildings and sealed enclosures.

What is SMPTE 311M cable?

SMPTE 311M is the standard hybrid camera cable for broadcast. It has two single-mode fibers for video and data, two power conductors and two control conductors in one jacket, and connects a camera to its camera control unit with SMPTE 304M connectors.

How long can a SMPTE 311M camera cable be?

The fiber can run for kilometres, but the copper power conductors limit the length because of voltage drop. The limit depends on the camera and CCU, so check the camera maker's published maximum, typically somewhere between several hundred metres and a few kilometres.

Are SMPTE 304M and ARIB connectors compatible?

No. SMPTE 304M connectors (usually in the LEMO 3K.93C format) and ARIB connectors used on many Japanese camera systems have different layouts and do not intermate. Adaptor cables exist; specify which system you use.

How far can 12G-SDI travel over coax?

Typically about 30 to 70 metres on a good RG6-class 75 ohm cable, depending on the cable and the receiving equipment's equaliser. For longer runs, convert to fiber, which carries 12G-SDI for kilometres on single-mode.

What is the difference between 3G-SDI and 12G-SDI?

3G-SDI (SMPTE 424M) runs at 2.97 Gb/s and carries 1080p at 50 or 60 frames per second. 12G-SDI (SMPTE ST 2082) runs at 11.88 Gb/s and carries 2160p (4K UHD) at 50 or 60 frames per second on a single link.

What does IP68 mean for a connector?

IP68 under IEC 60529 means the connector is dust-tight and protected against continuous immersion under conditions the manufacturer states, which must be harsher than IP67. The standard sets no fixed depth, so ask for the stated depth and duration. The rating applies when mated or capped.

What is the difference between IP67 and IP68?

Both are dust-tight. IP67 covers temporary immersion to 1 metre for 30 minutes. IP68 covers continuous immersion at a depth and duration stated by the manufacturer, which must be more severe than the IP67 test.

What is POF used for?

Plastic optical fiber is used for short control and data links in electrically noisy equipment: drives, inverters, power converters, wind turbine converters and PLCs. It gives complete electrical isolation, is easy to terminate, and typically runs up to about 50 metres.

What is the difference between POF and PCF?

POF has a 980 µm plastic core and suits links up to about 50 m. PCF, also called HCS, has a 200 µm silica core with a polymer cladding, much lower loss, and reaches a few hundred metres. Both are large-core fibers used for industrial control links.

What is the difference between Cat 6 and Cat 6A?

Cat 6 is specified to 250 MHz and supports 10GBASE-T only to about 37 to 55 metres. Cat 6A is specified to 500 MHz and supports 10GBASE-T to the full 100 metre channel. Both support gigabit Ethernet to 100 metres.

What is the maximum length of an Ethernet copper cable?

A TIA-568 twisted-pair channel is 100 metres: a 90 metre permanent link plus up to 10 metres of patch cords in total. Beyond that, use fiber.

Are military circular connectors RoHS compliant?

Not always. Olive drab cadmium plating, common on MIL-DTL-38999-style connectors, contains cadmium and is not RoHS compliant. Cadmium-free finishes such as zinc-nickel are available where RoHS compliance is required.

What does LSZH mean on a cable?

LSZH means low smoke zero halogen: the jacket gives off little smoke and no halogen acid gas when it burns. It is often required in data centres, ships, rail, tunnels and public buildings.